Description
Heat Shrink Bus-bar Insulation Tubing
Application
Used in medium voltage substations up to 36kV to reduce electric clearance and increase insulation between bus-bars
Feature
1.Anti-tracking
2.Excellent corrosion resistance
3.UV resistance and weathering resistance
4.Superior electrical and mechanical propertiesperformance.
Performance
Test | Test Method | Requirement |
Tensile strength | ASTM D 2671 | ≥11.8MPa |
Elongation at break | ASTM D 2671 | 700% |
tensile strength after heat aging | ASTM D 2671/120℃,168小h | ≥10MPa |
Elongation at break after heat aging | ASTM D 2671/120℃,168h | ≥500% |
Longitudinal shrinkage | ASTM D 2671 | 0 to-10% |
Electrical strength | IEC 243 | ≥20KV/mm |
Dielectric constant | IEC 250 | 3.0 Max |
Volume resistivity | IEC 93 | 1013Ω.cm |
Flame retardancy (oxygen index) | ASTM 4589 | ≥25 |
Copper corrosive 120 ° C, 168 hours | ASTM D 2671 | Pass |
Low temperature brittleness -40 ° C, 4 hours | ASTM D 2671 | No crack |
Water absorption rate | ISO 62/23℃,14 days | ≤0.5% |
Reviews